Checking Gas Appliance Input

Verifying Gas Input or Clocking the meter

1. Turn off the gas supply to all appliances other than the gas-fired boiler.
2. Note the rated manifold gas pressure listed on the boiler's rating label.
3. Connect the Manometer to the manifold pressure tapping on the Gas Valve (Figure F-1) to verify the input.
4. Light the main burners by adjusting the thermostat to the highest setting.
5. If required, adjust gas manifold pressure to the rated setting by turning the gas valve adjustment screw clockwise to decrease manifold pressure or counterclockwise to increase manifold pressure (Figure F-2). Several turns may be required.
6. On models using more than one gas valve, turn off the gas valve not having pilot control and first adjust the gas valve with pilot control. Then, turn on both gas valves and adjust the gas valve without pilot control.
7. Clock gas meter for at least two (2) revolutions of the dial, typically labeled ½ or 1 cubic foot per revolution on a residential gas meter.
8. Determine gas flow rate in Cubic Feet per Hour based on elapsed time for two revolutions. (Example: 70 Seconds for (2) Revolutions = 102.8 Cu. Ft.
9. When the clocked time falls between two table values (Table F-1), add the table values shown above and below your clocked reading and divide by 2 (Example:68 Seconds for (2) Revolutions = (110.7+102.8) /2 = 106.7 Cu. Ft./Hr.).
10.Obtain gas-heating value (Btu per cubic (foot) from gas supplier or use nominal value of 1000 Btu per cubic foot.
11. Multiply gas flow rate by gas heating value. (Example: 70 Seconds for (2) Revolutions = 120.8 Cu. Ft./Hr. X 1027 Btu/Cu. Ft. = 124,061 Btu/ Hr.
12. Compare the measured input rate to the input rates stated on the rating label. DO NOT EXCEED the boiler's rated gas maximum input pressure.
13. If the input is too high, reduce the input rate by decreasing the manifold pressure.

Alternate Calculation

1. Turn off all other appliances and pilot flames.
2. If the gas meter has a 1 Cubic Foot Gauge
3. Divide 3600 by the number of seconds for the 1 cu ft scale to make one revolution.
4. Multiply the above result by BTU of natural gas

Example:
40 seconds for 1 revolution
3600/40 = 90
90 * 1050 = 94,500

Disclaimer: The information found on this website is for informational purposes only. All preventive maintenance, service, and installations should be reviewed on a per-job basis. Any work performed on your heating system should be performed by qualified and experienced personnel only. Comfort-Calc or its personnel accepts no responsibility for improper information, application, damage to property, or bodily injury resulting from the application of information found on this website, as a professional should review it.