Buffer Tank Sizing forbidden without prior permission.">
Ask Boiler or System Questions. Leave Comments

Buffer Tank Sizing

We are showing how to size a buffer tank when you have an on/off or modulating boiler. When sizing the buffer tank, use the smallest zone and a predetermined run time. The runtime is at your discretion, typically ranging from 10 to 20 minutes.

Buffer tanks reduce boiler short cycling. Most boilers are normally 100% or more oversized for the heating system. If the boiler is properly sized, short cycling will automatically be reduced. When a high-efficiency boiler is used, the higher the turndown ratio, the less likely it is to require a buffer tank.

Let's look at sizing a buffer tank for an on/off boiler

V = t(Qhs - Qloadmin)/(500 * delta-T)

Where:

V =Minimum buffer tank volume (gallons)

t = Minimum heat source on time in minutes

Qhs = Rated heat output of heat source (Btu/h)

Qloadmin= Minimum concurrent heating load when heat source is in demand Btu/h

Delta-T = Change in average tank temperature during minimum heat source on time (f)

Let's assume the following:

t = 10-minute recovery time

Qhs = Boiler output 68,000

Qloadmin = Zone output 5000 Btuh/h

Delta-T = 20f

V = 10(68,000 - 5000) / (500 * 20f)

V = 63-gallon tank

 

Sizing a buffer tank for 80,000 Btu 10:1 high efficiency boiler

When calculating the minimum input of a high-efficiency boiler, divide the input by the turndown. Example of the above boiler,

Boiler input/turndown = minimum input

80,000/10 = 8000 minimum input

V = t(Qhsmin - Qloadmin)/(500 * delta-T)

Where:

V = Minimum buffer tank volume (gallons)

t = Minimum heat source on time in minutes

Qhsmin = Minimum stable heat output of heat source Btu/h

Qloadmin= Minimum concurrent heating load when heat source is in demand Btu/h

Delta-T = Change in average tank temperature during minimum heat source on time (f) Note: The smallest zone must be less than the minimum output of the boiler or no buffer tank is required.

Let's assume the following:

t = 10-minute recovery time

Qhsmin = Boiler output 8,000

Qloadmin = Zone output 2000 Btu/h

Delta-T = 20f

V = 10(8,000 - 2000) / (500 * 20f)

V = 6-gallon tank

Although this will run longer cycles, I am not happy with a high-efficiency boiler running a minimum of 10 minutes. I would choose 15 - 20 minutes run times.

The difference would be if all were the same except for a 20-minute run time. would be as follows.

V = 20(8,000 - 2000) / (500 * 20f)

V = 12-gallon tank

You can see that getting a better run time would not be a drastic tank size change. You can see that changing the delta-T will change the tank size and run time.

What if our boiler of choice is an 80,000 Btu/h output 5:1 turndown boiler.

Let's apply this.

V = 10(18,000 - 2000) / (500 * 20f)

V = 16-gallon tank

But, a 20-minute runtime would change the tank size to:

V = 20(18,000 - 2000) / (500 * 20f)

V = 32-gallon tank

We'll add one more idea. Let's change the Delta-T to 30f

V = 20(18,000 - 2000) / (500 * 30f)

V = 21.3-gallon tank

Changing run times or tank delta-Ts will change the tank size. You can adjust the numbers to find the best fit for your application.

Download Excel Buffer Tank Sizing Worksheet


After downloading, open the form and enter the appropriate information in the green boxes on the worksheet.

Disclaimer: The information found on this website is for informational purposes only. All preventive maintenance, service, and installations should be reviewed on a per-job basis. Any work on your heating system should be performed only by qualified, experienced personnel. Comfort-Calc and its personnel accept no responsibility for improper information, application, damage to property, or bodily injury from applied information found on this website.