Troubleshooting Outdoor Reset Problems
We will start with a scenario that the homeowner has been happy with thr boiler operation along with Outdoor Reset (ODR). Nobody has worked on the boiler since the last boiler service and now he realizes the house is not as warm as it has been and the room temperature does not meet thermostat setpoint. What do you do?
1. OD sensor Problem
A. Verify the sensor is still fastened to the wall at it's original location. I have seen situations where they were removed or moved and sometimes without the owner even knowing it. Usually by siding contractors or landscapers knocking them off the wall. If missing the control should give an error code.
B. Disconnect the OD sensor using the Ohms setting. Select the next scale above 10K or closest to 10 as long as it is above 10K. If your meter is self scaling just choose ohms and it will choose the correct scale.
C. Make a note of this and compare this reading to the current outdoor temperature near the sensor. The reading should be close to the chart for the OD sensor.
D. You will be able to read your ohms reading and see what temperature the ohms reading is returning by reading to the left to the temperature column. It may not be exact but within a few decrees is fine.
E. If reading is off replace the sensor with the same type.
2. Check the wire
A. Reconnect the sensor to the wire. At the boiler remove the sensor wires from the boiler terminals
B. Do the same test as you did on the sensor only, leave it connected to the wire. The reading should be pretty close. Compare to the chart.
C. What changed in the basement? Did they add fluorescent lights or anything that is near enough to the sensor wire that would affect it's reading? If the sensor wire is wrapped with a small metal wrap, it is known as shielded cable, it should not be affected. Try replacing the sensor, the extra resistance may be affecting the sensor.
1. OD sensor problem
A. Follow the same steps as #1. above
2. Check the wire
A. Follow the same steps as #2A. above, The sensor should be mounted outside on a North or East wall and above the snow level.
B. Follow the same steps as #2B. above. If the reading is much different to the sensor alone reading proceed to 2C.
C. The wire should be shielded cable., if not how is the wire routed between the sensor and the boiler? It should run perpendicular (cross over) to line voltage wires not parallel (beside, along) with them.
D. Is the wire routed near an electrical breaker box, fluorescent lights, projection TV's, large screen TV's or anything else that could interfere with the ohm's reading. Do not wrap the sensor wire around anything including other wires or conduit with wires inside it.
E. If using shielded cable, is a small amount of the metal coating unraveled and attached to a metal surface to ground it?. If not it needs to be grounded.
2. Review the parameters
A. Verify the ODR is not disabled
B. Verify all the parameters are set properly. To review parameter descriptions and settings Click Here.
Disclaimer: The information found on this website is for informational purposes only. All preventive maintenance, service, installations should be reviewed on a per job situation. Any work performed on your heating system should be performed by qualified and experienced personnel only. Comfort-Calc or its personnel accepts no responsibility for improper information, application, damage to property or bodily injury from applied information found on this website as it should be reviewed by a professional.